Prime Power Generators: Genset J88K

Model

J88KM

70 KW/88 kVA

64 kW / 80 kVA

Stand-by Power @ 50 Hz

Prime Power @ 50 Hz

Standard Features

J88K Photo
  • Engine (JOHN DEERE , 4045TF220 )
  • Charge alternator 12 V, Governor: Meca
  • Alternator (LEYROY SOMRER , LSA432L8 )
  • Single bearing alternator IP 23 , insulation class H /H
  • Radiator 50°C [122°F] °C max. T° air inlet with coolant cap
  • Skid and vibration isolators
  • Dry type air filter
  • Microprocessor control panel
  • Main line circuit breaker
  • 12 V battery, rack and cable
  • Industrial silencer (loose)
  • User manual

Generator Ratings

VoltageHZPhasePFStand By AmpsStand by power kW/kVAPrime Power kW/kVA
415/240 MONO V 50 Hz 3 0.8 122 70/88 64/80
400/230 MONO V 50 Hz 3 0.8 127 70/88 64/80
380/220 MONO V 50 Hz 3 0.8 129 68/65 62/77
240/120 MONO V 50 Hz 3 0.8 212 70/88 64/80
230/115 MONO V 50 Hz 3 0.8 221 70/88 64/80
220/110 MONO V 50 Hz 3 0.8 231 70/88 64/80
220/127 MONO V 50 Hz 3 0.8 202 62/77 56/70
200/115 MONO V 50 Hz 3 0.8 254 70/88 64/80

PRP: Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046-1

ESP:The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO8528-1. Overload is not allowed.

Conditions of sales

  • SDMO provides a full line of products with high quality recognized engines and alternators.
  • Service and parts are available from SDMO distributors as a single source of responsibility.
  • Each and every units is factory tested. All generator sets are also prototype tested.
  • Warranty according to our standard conditions. Five years extended also available.

Call Us on 01794 521355

J88K specifications and design liable to modifications without prior notice


Engine Specifications

Engine Data

Manufacturer / Model :

4045TF220, 4-cycle, Turbo, N/A

Cylinder Arrangement :

4 X L

Displacement :

4.48L [273.0C.I.]

Bore and Stroke :

106mm [4.2in.] X 127mm [5in.]

Compression ratio :

17 : 1

Rated RPM :

1500 Rpm

Piston Speed :

6.35m/s [20.8ft./s]

Max. stand by Power at rated RPM :

80kW [107BHP]

Frequency reg, steady state :

+/-2, 5%

BMEP :

13.3bar [193psi]

Governor type:

Meca

 

Exhaust System

Exhaust gas flow :

205L/s [434cfm]

Exhaust temperature :

565°C [1049°F]

Max back pressure :

750mm CE [25in. WG]

 

Feul System

110% (Stand By power ) :

21.5L/h [5.7gal/hr]

100% (of the Prime Power) :

19.5L/h [5.2gal/hr]

75% (of the Prime Power) :

14L/h [3.7gal/hr]

50% (of the Prime Power) :

10L/h [2.6gal/hr]

Total fuel flow :

108L/h [28.5gal/hr]

 

Oil System

Total oil capacity w/filters :

13.5L [3.6gal]

Oil Pressure low idle :

1bar [14.5psi]

Oil Pressure rated RPM :

5bar [72.5psi]

Oil consumption 100% load :

0.019L/h [0.0gal/hr]

Oil capacity carter :

12.5L [3.3gal]

 

Thermal balance 100% load

Heat rejection to exhaust :

65kW [3696Btu/mn]

Radiated heat to ambiant :

9.5kW [540Btu/mn]

Heat rejection to coolant :

43kW [2445Btu/mn]

 

Air intake

Max. intake restriction :

625mm CE [25in. WG]

Engine air flow :

93L/s [107cfm]

 

Coolant System

Radiator & engine capacity :

23.6L [6.2gal]

Max water temperature :

105°C [221°F]

Outlet water temperature :

93°C [199°F]

Fan power :

2.5 kW

Fan air flow :

3.37m3/s [7141cfm]

Available restriction on air flow :

20mm CE [0.8in. WG]

Type of coolant :

Gencool

Thermostat :

82-94 °C(179-201.2°F)

 

Emissions

HC(mg/Nm3) :

34 mg/Nm3

CO(mg/Nm3) :

190 mg/Nm3

Nox(mg/Nm3) :

3800 mg/Nm3

PM(mg/Nm3) :

60 mg/Nm3

 

Call Us on 01794 521355

J88K specifications and design liable to modifications without prior notice


Alternator Specifications

General Data

  • Compliance with NEMA MG21, UTE NF C51.111, VDE 0530, BS 4999, CSA standards.
  • Vacuum-impregnated windings with epoxy varnish.
  • IP21 drip proof.

Alternator

Manufacturer / Type :

LEROY SOMER LSA432L8

Number of phase :

3

Power factor (Cos Phi) :

0.8

Altitude :

<1000 m

Overspeed :

2250 rpm

Pole Number :

4

Exciter type :

Shunt

Insulation class, temperature rise :

H/H

Voltage regulator :

R230

Sustained short circuit current:

Total harmonics (TGH/THC)

<4%

Wave form : NEMA = TIF – TGH/THC

<50

Wave form : CEI = FHT – TGH/THC :

<2%1

Bearing – number :

1

Coupling :

Direct

Voltage regulation 0 to 100% load :

+/- 1%

Recovery time (20% Volt dip) ms

500 ms

SkVA with 90 % of nominal sustained voltage (at 0.4 PF) :

270
 

 

Other Alternator Data

Continuous nominal rating @ 40°C :

80 kVA

Standby rating @ 27°C :

88 kVA

Efficiencies @ 4/4 load :

90.5 %

Air flow(m3/s ) :

0.27m3/s [572.09cfm]

Short circuit ratio (Kcc) :

0.41

Direct axis synchro reactance unsaturated (Xd) :

290 %
 

Quadra axis synchro reactance unsaturated (Xq) :

174 %

Open circuit time constant (T'do) :

1431 ms

Direct axis transient reactance saturated (X'd) :

10.1 %

Short circuit transient time constant (T'd) :

50 ms

Direct axis subtransient reactance saturated (X''d) :

5 %

Subtransient time constant (T''d)

5 ms

Quadra axis subtransient reactance saturated (X''q)

5 %

Zero sequence reactance unsaturated (Xo) :

0.2 %
 

Negative sequence reactance saturated (X2) :

5.7 %

Armature time constant (Ta) :

1 ms

No load excitation current (io) :

0.4 A

Full load excitation current (ic) :

1.6 A

Full load excitation voltage (uc) :

29V

Recovery time (Delta U = 20% transitoire) :
 

500ms
 

Motor start (Delta = 20% perm. Or 50% trans.):

240 kVA

Transient dip (4/4 charge) – PF : 1.8 AR :

13.9%

No load losses :

1.41kW[1.41Kw]

Heat rejection :

6.64 kW

 

Call Us on 01794 521355

J88K specifications and design liable to modifications without prior notice

Optional Conrol Panels

Standard panel : NEXYS


Specifications :
Frequency meter, Ammeter, Voltmeter
Alarms and faults :
Oil pressure, water temperature, Overcrank, Overspeed ( >60 kVA), Min/max, alternator, Low fuel level, Emergency stop
Engine parameters :
Hours counter, Engine speed, Battery voltage, Fuel level, AIr preheating

Standard panel : TELYS


Specifications :
Frequency meter, Ammeter, Voltmeter
Alarms and faults :
Oil pressure, water temperature, No start-up, Overspeed, Min/max alternator, Min/max battery voltage, Low fuel level, Emergency stop
Engine parameters :
Hours counter, Oil pressure, Water temperature, Engine speed, Battery voltage, Fuel level
 

Options

Engine and Radiator

  • Heat shield protection
  • Oil drain extension
  • Heavy duty air filter
  • Lube oil drain pump
  • Radiator core guard
  • Battery charger
  • Block heater
 

Alternator

  • Anti condensation heater
  • Enforced impregnation
  • Oversized alternator
 

Control panel

  • NFPA 110 level 1
  • Paralleling system
  • Remote annunciator
  • Oil temperature shutdown
  • Key start panel
 

Exhaust

  • Residential silencer
  • Critical silencer
  • Flexible exhaust conn.
 

Fuel

  • Day tank
  • Subbase fuel tanks UL
  • Water separator fuel filter
 

Enclosure M127

  • Silent 70 db @ 7m [23 Ft] (stby)
 

Literature

  • Parts
  • Maintenance
 

Weight & Dimensions

Open Model

Open Model Diagram

Overall size l x w x h : 1870mm [74in] x 994mm [39in] x 1360mm [54in]

Weight : 1110kg [2446lbs] Net 1310kg [2887lbs] Brut

 

With optional Exclosure

Overall size l x w x h : 2300mm [91in] x 1080mm [43in] x 1680mm [66in]

Weight : 1530kg [3372lbs] Net 1730kg [3813lbs] Brut

Call Us on 01794 521355

J88K specifications and design liable to modifications without prior notice

Printer IconPrint This Page